| Plan Review Notes For Permit 14071212 |
| Permit Number |
14071212 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-15 07:19:43 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | MECHANICAL | | | | | | 1) PROVIDE EQUIPMENT SIZING CALCULATIONS BASED ON THE | | | ACTUAL BUILDING ORIENTATION FOR THIS LOT, AS REQUIRED | | | BY SECTION 403.6 OF THE 2010 FBC - ENERGY CONSERVATION. | | | THE CALCULATIONS THAT WERE SUBMITTED AND THE EQUIPMENT | | | LISTED ON THE A/C PLAN ARE FOR WORST CASE. | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | 2014-08-20 14:50:55 | LOADED AND REVIEWED BY RBERGSMA |
|