| 2014-09-11 10:02:12 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | BUILDING |
| | |
| | 1) THE ENERGY COMPLIANCE FORM THAT WAS SUBMITTED FOR |
| | THIS SINGLE FAMILY DWELLING IS WORST CASE AND DOES NOT |
| | MATCH THE ORIENTATION OF THE STRUCTURE. THE HVAC LOAD |
| | CALCULATIONS THAT WERE SUBMITTED SPECIFY THAT THE FRONT |
| | DOOR FACES NORTHEAST. BASED ON THE SURVEY THAT WAS |
| | SUBMITTED, THE FRONT DOOR FACES WEST. FBC ENERGY |
| | CONSERVATION 403.6.1 |
| | |
| | 2) IDENTIFY THE ELEVATION THAT WILL BE USED FOR THIS |
| | DWELLING AND CROSS OUT THE OTHERS. FBC 107.2.1 |
| | |
| | 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | PROVIDE PRODUCT APPROVALS FOR THE ROOF TILE |
| | UNDERLAYMENT AND THE 6 FOOT WIDE OVERHEAD GARAGE DOOR. |
| | THE SLIDING GLASS DOOR NOA NO. 11- 1018.14 AND THE ROOF |
| | TILE ADHESIVE NOA NO. 12-0228.18 HAVE BEEN SUPERSEDED. |
| | THE FIXED WINDOW NOA NO. 13-0502.03 ONLY HAD 9 COPIES |
| | OF THE FIRST PAGE. THE INSTALLATION DRAWINGS ARE |
| | MISSING. |
| | |
| | 4) SPECIFY THE REQUIRED EMBEDMENT DEPTH OF THE 3/4" |
| | DIA. ANCHOR BOLTS FOR THE COLUMN BASE IN DETAIL 1 ON |
| | S-1. |
| | |
| | 5) FBC 109.3 THE VALUATION ON THE APPLICATION OF |
| | $239,116.00 IS LOW AND HAS BEEN ADJUSTED TO $432,598.00 |
| | BASED ON THE LATEST ICC VALUATION DATA. |
| | |
| | 6) THE ENERGY CALCULATIONS LIST INSULATED DOORS FOR THE |
| | DOORS WITH GLASS INSERTS. THE SIMULATED PERFORMANCE |
| | METHOD SECTION 405.5.1 REQUIRES ALL GLAZING IN DOORS TO |
| | BE INCLUDED IN THE TOTAL WINDOW AREA. 405.5.3 DOORS |
| | WITH GLAZING. FOR DOORS THAT ARE OPAQUE OR WHERE THE |
| | GLASS IS LESS THAN ONE-THIRD OF THE AREA OF THE DOOR, |
| | THE TOTAL DOOR AREA SHALL BE INCLUDED IN THE DOOR |
| | CALCULATION. FOR UNLABELED SLIDING GLASS DOORS OR WHEN |
| | GLASS AREAS IN DOORS IS GREATER THAN OR EQUAL TO |
| | ONE-THIRD OF THE AREA OF THE DOOR, THE GLAZING PORTION |
| | SHALL BE INCLUDED IN THE GLAZING CALCULATION AND THE |
| | OPAQUE PORTION OF THE DOOR SHALL BE INCLUDED IN THE |
| | DOOR CALCULATION. WHEN GLASS AREA IN DOORS IS GREATER |
| | THAN OR EQUAL TO ONE-THIRD OF THE AREA OF THE DOOR, THE |
| | DOOR SHALL BE INCLUDED IN THE GLAZING CALCULATION AS A |
| | TOTAL FENESTRATION USING THE TESTED U-FACTOR AND SOLAR |
| | HEAT GAIN COEFFICIENT. |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |