2014-09-11 10:02:12PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE ENERGY COMPLIANCE FORM THAT WAS SUBMITTED FOR
 THIS SINGLE FAMILY DWELLING IS WORST CASE AND DOES NOT
 MATCH THE ORIENTATION OF THE STRUCTURE. THE HVAC LOAD
 CALCULATIONS THAT WERE SUBMITTED SPECIFY THAT THE FRONT
 DOOR FACES NORTHEAST. BASED ON THE SURVEY THAT WAS
 SUBMITTED, THE FRONT DOOR FACES WEST. FBC ENERGY
 CONSERVATION 403.6.1
  
 2) IDENTIFY THE ELEVATION THAT WILL BE USED FOR THIS
 DWELLING AND CROSS OUT THE OTHERS. FBC 107.2.1
  
 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE PRODUCT APPROVALS FOR THE ROOF TILE
 UNDERLAYMENT AND THE 6 FOOT WIDE OVERHEAD GARAGE DOOR.
 THE SLIDING GLASS DOOR NOA NO. 11- 1018.14 AND THE ROOF
 TILE ADHESIVE NOA NO. 12-0228.18 HAVE BEEN SUPERSEDED.
 THE FIXED WINDOW NOA NO. 13-0502.03 ONLY HAD 9 COPIES
 OF THE FIRST PAGE. THE INSTALLATION DRAWINGS ARE
 MISSING.
  
 4) SPECIFY THE REQUIRED EMBEDMENT DEPTH OF THE 3/4"
 DIA. ANCHOR BOLTS FOR THE COLUMN BASE IN DETAIL 1 ON
 S-1.
  
 5) FBC 109.3 THE VALUATION ON THE APPLICATION OF
 $239,116.00 IS LOW AND HAS BEEN ADJUSTED TO $432,598.00
 BASED ON THE LATEST ICC VALUATION DATA.
  
 6) THE ENERGY CALCULATIONS LIST INSULATED DOORS FOR THE
 DOORS WITH GLASS INSERTS. THE SIMULATED PERFORMANCE
 METHOD SECTION 405.5.1 REQUIRES ALL GLAZING IN DOORS TO
 BE INCLUDED IN THE TOTAL WINDOW AREA. 405.5.3 DOORS
 WITH GLAZING. FOR DOORS THAT ARE OPAQUE OR WHERE THE
 GLASS IS LESS THAN ONE-THIRD OF THE AREA OF THE DOOR,
 THE TOTAL DOOR AREA SHALL BE INCLUDED IN THE DOOR
 CALCULATION. FOR UNLABELED SLIDING GLASS DOORS OR WHEN
 GLASS AREAS IN DOORS IS GREATER THAN OR EQUAL TO
 ONE-THIRD OF THE AREA OF THE DOOR, THE GLAZING PORTION
 SHALL BE INCLUDED IN THE GLAZING CALCULATION AND THE
 OPAQUE PORTION OF THE DOOR SHALL BE INCLUDED IN THE
 DOOR CALCULATION. WHEN GLASS AREA IN DOORS IS GREATER
 THAN OR EQUAL TO ONE-THIRD OF THE AREA OF THE DOOR, THE
 DOOR SHALL BE INCLUDED IN THE GLAZING CALCULATION AS A
 TOTAL FENESTRATION USING THE TESTED U-FACTOR AND SOLAR
 HEAT GAIN COEFFICIENT.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  