| Plan Review Notes For Permit 14071168 |
| Permit Number |
14071168 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-14 18:42:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723. | | | | | | 2. RENOVATIONS TO A HIGH RISE BUILDING ARE NOT INCLUDED | | | IN THE SCOPE OF A CRC LICENSE, SEE FLORIDA STATUTE 489. | | | | | | 3. THE PERMIT APPLICATION WAS SUBMITTED IN PENCIL. | | | APPLICATIONS ARE TO BE COMPLETED IN INK. THE NAME OF | | | THE OWNER HAS BEEN ERASED AND REWRITTEN. THIS IS NOT AN | | | ACCEPTABLE PERMIT APPLICATION, FBC 107. | | | | | | 4. THE DBA (COMPANY NAME) ON THE APPLICATION IS "FLOOR | | | SPECIALISTS." THIS COMPANY IS NOT REGISTERED. | | | | | | | | | | | | | | | |
|