2014-08-02 13:53:06DATE: 8/2/2014
 PROJECT: UNCLE BOB'S STORAGE
 PERMIT#: 14071167
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION REQUIRED. FBC WPB AMENDMENTS.
 107.2.3
  
 NEC 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED
 AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.
 (B) RATING. BRANCH CIRCUITS THAT SUPPLY SIGNS SHALL BE
 RATED IN ACCORDANCE WITH 600.5(B)(1) OR (B)(2).
 (1) INCANDESCENT AND FLUORESCENT. BRANCH CIRCUITS THAT
 SUPPLY SIGNS AND OUTLINE LIGHTING SYSTEMS CONTAINING
 INCANDESCENT AND FLUORESCENT FORMS OF ILLUMINATION
 SHALL BE RATED NOT TO EXCEED 20 AMPERES.
 (2) NEON. BRANCH CIRCUITS THAT SUPPLY NEON TUBING
 INSTALLATIONS SHALL NOT BE RATED IN EXCESS OF 30
 AMPERES.
  
 THE ABOVE ARTICLE 600.5 QUOTED FROM THE 2008 EDITION OF
 THE NEC STATES THAT THE RATING OF THE BRANCH CIRCUIT IS
 DIRECTLY PROPORTIONAL TO THE TYPE OF LOAD IT IS
 CONNECTED TO. PLEASE PROVIDE THE MANUFACTURER'S DATA
 SHEETS ON THE SIGN THAT IS PROPOSED TO BE INSTALLED TO
 DETERMINE THE TYPE AND SIZE OF THE LOAD ASSOCIATED WITH
 IT THEREBY DETERMINING THE SIZE AND RATING OF THE
 BRANCH CIRCUIT TO INSTALL TO CONNECT IT TO.
  
 NEC 600.7(1) SIGNS AND METAL EQUIPMENT OF OUTLINE
 LIGHTING SYSTEMS SHALL BE GROUNDED BY CONNECTION TO THE
 EQUIPMENT GROUNDING CONDUCTOR OF THE SUPPLY BRANCH
 CIRCUIT(S) OR FEEDER USING THE TYPES OF EQUIPMENT
 GROUNDING CONDUCTORS SPECIFIED IN THE NEC 250.118.
  
 PROVIDE AND INDICATE ON THE PLANS THAT AN EQUIPMENT
 GROUNDING CONDUCTOR WILL BE ROUTED WITH THE SUPPLY
 CONDUCTORS AND SIZRED IN ACCORDANCE WITH THE NEC
 250.118 FOR CONNECTION TO THE SIGN AS REQUIRED BY NEC
 600.7 AS INDICATED ABOVE.
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 PROVIDE AND INDICATE ON THE PLANS HOW THE SIGN CIRCUIT
 WILL BE CONTROLLED IN ORDER TO MEET THE INTENT OF THE
 FBC-E SECTION 505.2.4 AS INDICATED ABOVE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  