Text |
| 2014-11-02 08:05:23 | 1) SHT.A-0.0 - BUILDING CODE BLOCK - YOU HAVE NOW |
| | CLASSIFIED THE STRUCTURE AS A "MIXED OCCUPANCY". THERE |
| | IS NO SUCH GENERAL CLASSIFICATION IN CHAPTER 3 OF THE |
| | FBC. THE DIFFERENT TYPES OF OCCUPANCIES MUST BE |
| | LISTED.MY PREVIOUS COMMENT ASKED TO CLARIFY AS TO HOW |
| | THE BUILDING COULD BE CLASSIFIED AS ONE TYPE OF |
| | OCCUPANCY WHEN IT WAS ACTUALLY A MIXED OCCUPANCY OF |
| | SEVERAL CLASSIFICATIONS. I DID NOT REQUEST THAT THE |
| | OCCUPANCY BE CHANGED, ONLY TO CLARIFY THE |
| | CLASSIFICATION THAT YOU PLACED ON THE STRUCTURE. IF YOU |
| | WOULD HAVE NOTED ON THE PREVIOUS SET THAT IT WAS THE |
| | MOST RESTRICTIVE I WOULD NOT HAVE RAISED THE QUESTION. |
| | 2) 2ND REQUEST - SUBMIT A GAS RISER DIAGRAM FOR |
| | REVIEW.SHOW THE TYPE OF PIPING MATERIAL, LENGTHS OF |
| | EACH PIPE SECTION, BTU LOAD OF EACH APPLIANCE & TOTAL |
| | BTU LOAD ON THE SYSTEM, COMBUSTION AIR REQUIREMENTS, |
| | VENTING, LOCATION OF VALVES, REGULATORS, ETC. OR PLACE |
| | A NOTE ON BOTH SETS OF PLANS THAT GAS SHALL BE UNDER A |
| | SEPARATE PERMIT. |
| | 3) 2ND REQUEST - SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS FOR ALL GAS EQUIPMENT & APPLIANCES. APPLIANCES |
| | SHALL BE LISTED AND LABELED PER THE 2010 FGC SEC.301.3. |
| | 4) THE REQUIRED CLEARANCE AROUNFD A WATER CLOSET SHALL |
| | BE A MINIMUM OF 60 INCHES MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. YOU HAVE A DIMENSION |
| | OF 5 FT. BY 4FT-6 INCHES WHICH DOES NOT COMPLY. REFER |
| | TO THE THE 2010 FL. ACCESS. CODE SEC. 604.3. YOU ONLY |
| | NEED TO SHOW THESE DIMENSIONS ONCE ON THE ENLARGED |
| | TOILET ROOM PLAN ON SHT.A-1.2. |
| | 5) THE GREASE TRAP SHALL BE CONSTRUCTED IN ACCORDANCE |
| | WITH THE 2010 FPC SEC.1003.3.4. 2ND REQUEST. SUBMIT |
| | DETAILS. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |