| Date |
Text |
| 2014-09-02 12:29:21 | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. |
| | 1) SHT. A-0.0- CODE SUMMARY BLOCK - REFERENCE IS MADE |
| | TO THE 2010 FLORIDA BUILDING CODE W/ BOCA RATON |
| | AMENDMENTS. REVISE THIS TO READ CITY OF WEST PALM |
| | BEACK. |
| | 2) THE ADDRESS OF THE PROJECT ON THE APPLICATION DOES |
| | NOT MATCH THE ADDRESS ON THE PLANS. CORRECT THE PLANS |
| | TO REFLECT THE CORRECT ADDRESS. |
| | 3) SHT. A-0.0- BUILDING CODE BLOCK- THIS PROJECT IS |
| | NOTED AS AN A-2 OCCUPANCY. IT IS ACTUALLY A MIXED |
| | OCCUPANCY OF SEVERAL CLASSIFICATIONS SUCH AS A-1, A-3, |
| | A-4, B,ETC. HOW CAN THIS BUILDING BE CLASSIFIED AS AN |
| | A-2 IN IT'S ENTIRETY? CLARIFY.2010FBC SEC.508.1 |
| | 4) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES SHALL BE |
| | BASED ON THE DIFFERENT OCCUPANCIES. 2010 FPC SEC.403.1. |
| | I AM QUESTIONING YOUR AREA PER PERSON CALCULATIONS ON |
| | SHT. A-0.0- UNTIL YOU REVISE THE OCCUPANCIES & OCCUPANT |
| | LOAD, THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES |
| | CANNOT BE DETERMINED |
| | A) CONCESSION AREA - WHERE ARE YOU GETTING THE 200 SQ. |
| | FT. PER PERSON FROM? |
| | B) BOWLING AREA- SHOULD BE 7 SQ. FT. PER PERSONPER FBC |
| | TABLE 1004.1 |
| | C) THEATRE LOBBY- SHOULD BE 5 SQ. FT. PER PERSON NET |
| | FOR STANDING AREA. |
| | 5) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS |
| | APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER |
| | THE 2010 FGC SEC.301.3. |
| | 6) SUBMIT A GAS RISER FOR REVIEW. SHOW TYPE OF PIPING |
| | MATERIAL, LENGTHS OF EACH PIPE SECTION, BTU |
| | LOAD,COMBUSTION AIR, VENTING, LOCATION OF VALVES, |
| | METER, REGULATOR, ETC.2010 FGC SECS.304,402.1,. |
| | 7) SHOW THE REQUIRED DIMENSIONS OF THE CLEAR FLOOR |
| | SPACES FOR THE HANDICAPPED URINAL AND FOR THE FIXTURES |
| | IN THE ACCESSIBLE TOILET ROOMS.2010 FAC SEC., 305. |
| | 8) SHT. A-1.2- A MINIMUM 30" X 60 " CLEARANCE SHALL BE |
| | PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER |
| | COMPARTMENT PER THE 2010 FAC SEC.608.2.2.1. |
| | 9) SHT.A-1.2- SHOW THE LOCATION OF THE GRAB BARS IN THE |
| | ACCESSIBLE SHOWERS.COMPLY W/ FAC SEC. 608.3.3. |
| | 10) THE LOCATION OF THE SHOWER SPRAY UNIT (HEIGHT) |
| | SHALL COMPLY WITH THE 2010 FAC SEC.608.5.3. THE MAX. |
| | HEIGHT IS 48 INCHES ABOVE THE SHOWER FLOOR. |
| | 11) SHT. A-1.2 - THERE IS A NOTE ON THE PLAN THAT |
| | REFERS TO INTERIOR DESIGN DRAWINGS FOR LOCATIONS AND |
| | MOUNTING HEIGHTS OF ITEMS IN THE RESTROOMS. THERE ARE |
| | NO INTERIOR DESIGN DRAWINGS IN THE PLANS. SUBMIT THESE |
| | DRAWINGS FOR REVIEW. |
| | 12) SHT. A-1.2- THE REAR WALL AND SIDE WALL GRAB BARS |
| | SHALL COMPLY W/ THE 2010 FAC SECS. 604.5.1 & 604.5.2. |
| | 13)SHT. A-1.2- THE MOUNTING HEIGHT OF THE TOILET PAPER |
| | DISPENSER SHALL COMPLY W/ THE 2010 FAC SEC.604.7. |
| | 14) SHT. A-1.2.- THE DOOR FOR THE AMBULATORY |
| | COMPARTMENT STALL SHALL NOT SWING INTO THE STALL PERR |
| | THE 2010 FAC SEC.604.8.2.2. |
| | 15) SHT.A-4.1- SUBMIT A STORM WATER RISER FOR REVIEW. |
| | THE SQUARE FOOTAGE OF THE AREAS OF THE SLOPED ROOFS |
| | THAT DRAIN ONTO THE FLAT ROOF SHALL BE INCLUDED IN THE |
| | TOAT SQUARE FOOTAGE FOR THE SIZING OF THE STORM SYSTEM. |
| | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.3.5.1.3. |
| | 16) SHT. A-4.1- VERTICAL LEADER CALCULATIONS- WHERE |
| | DOES THE 114 SQ. FT. COME FROM? |
| | 17) SHT. A-4.1 - SCUPPERS SHALL BE SIZED PER THE 2010 |
| | FPC SEC.1106.7 & TABLE 1106.7. SUBMIT CALCULATIONS AS |
| | TO HOW YOU ARRIVED AT THE STATED SIZES. |
| | 18) SHT. A-4.1-FLAT ROOF NOTES- NOTE #8- SCUPPERS SHALL |
| | NOT HAVE AN OPENING LESS THAN 4 INCHES PER THE 2010 FPC |
| | SEC.1107.3. |
| | 19) SIZE ALL SECTIONS OF THE SANITARY RISER- ( WET |
| | SECTIONS OF URINALS, LAVS, HORIZONTAL BRANCH FOR THE |
| | DRINKING FOUNTAINS, SIZE ALL SECTIONS OF THE FIXTURE |
| | BRANCHES). |
| | 20) THE DEVELOPED LENGTH FOR THE 2" VENT FROM THE MEN'S |
| | RESTROOM WATER CLOSETS TO WHERE IT CONNECTS TO THE 3" |
| | VTR APPEARS THAT IT MAY EXCEED 40 FT. IN LENGTH. IF SO, |
| | THE 2" VENT SHALL BE INCREASED TO 3" FOR IT'S ENTIRE |
| | LENGTH PER THE 2010 FPC SEC.916.2. SHOW THE DEVELOPED |
| | LENGTH ON THE SANITARY RISER. |
| | 21) SHOCK ARRESTORS ARE REQUIRED ON THE REFRIGERATOR |
| | ICE LINE. 2010 FPC SEC.604.9. |
| | 22) SUBMIT CONSTRUCTION SPECIFICATIONS FOR THE GREASE |
| | INTERCEPTOR.COMPLY W/2010 FPC SEC.1003.3.4. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE- |
| | CHIEF PLUMBING INSPECTOR |
| | TEL:561-805-6692 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |