| 2014-08-18 11:29:53 | 8/18/14 | | | NOTES: | | | 1.PAGE 9OF 9 OF THE ENERGY CALCULATIONS MUST BE | | | COMPLETELY FILLED OUT. | | | 2.INDICATE ON THE A/C SCHEDULE THE EER/SEER OF THE A/C | | | EQUIPMENT AS REQUIRED BY THE ENERGY CALCULATIONS. | | | 3.PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | | THE FIRE PLACE. | | | 4..SHOW ON PLANS COMPETE DETAIL OF THE CONDENSING UNIT | | | INSTALLATION ON THE ROOF AND INDICATE HOW THE STAND IS | | | SECURED TO ROOF AND THE UNIT TO THE STAND. | | | 5.PROVIDE COMPLETE KITCHEN EXHAUST HOOD INSTALLATION | | | DATAILS(TYPE 1) AS REQUIRED BY FMC SEC.506 AND 507. | | | 6.PROVIDE COMPLETE FIRE SUPPRESSION PLANS AS REQUIRED | | | BY THE FMC SEC.509. | | | 7.SHOW ON PLANS THE DISCHARGE LOCATION OF THR | | | CONDENSATE AS REQUIRED BY SEC.307 OF THE FMC AND | | | SEC.1503.7 OF THE FBC. | | | | | | REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT | | | 561-805-6732. |
|