| Plan Review Notes For Permit 14071105 |
| Permit Number |
14071105 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-14 13:51:18 | | | | 14071105 | | | 1517 CAMERON SAMUEL LANE | | | CLUBHOUSE BUILDING | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN | | | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. PROVIDE A FIXTURE SCHEDULE FOR THE | | | LIGHTING SYSTEM. FBC ENERGY CONSERVATION 505.5; | | | 505.5.3; T. 505.5.3 | | | | | | CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING | | | CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE | | | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL | | | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME | | | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST | | | 10 HOURS. FBC ENERGY CONSERVATION 505.2 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 | | | | | | PANEL P1 AND P2 MAY NOT BE LOCATED IN A STORAGE ROOM. | | | PANEL BOARDS SHALL BE LOCATED IN DEDICATED SPACES. NEC | | | 240.24(D), 110.26 (A) THRU (G). | | | | | | RECEPTACLES LOCATED OUTSIDE ADJACENT TO THE LOGGIA | | | REQUIRE GFCI PROTECTION. NEC 210.8 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-805-6700 | | | | | | | | | |
|