Plan Review Notes
Plan Review Notes For Permit 14071005
Permit Number 14071005
Review Stop B
Sequence Number 2
Notes
Date Text
2014-10-22 16:16:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE REFER TO EMAIL FROM 8/19 (A COPY IS INCLUDED
 BELOW) - A PRELIMINARY COURTESY REVIEW WAS DONE FOR THE
 ELEVATION CERTIFICATE SENT VIA EMAIL.
  
 CONTRACTOR IS TO INDICATE WHICH VENT IS INSTALLED,
 PRIOR TO PERMIT ISSUANCE.
  
 AFTER PERMIT ISSUANCE, PHOTOGRAPHS WILL BE REQUIRED
 PRIOR TO FINAL INSPECTION OR HAVE THE SURVEYOR INDICATE
 WHICH VENT MODEL IS INSTALLED. I WAS UNABLE TO LOCATE A
 PERMIT FOR THIS WORK (CHECKED 06040626 AND 07040908).
 THE ELEVATION CERTIFICATE SUBMITTED WITH PERMIT
 07040908 SHOWS 0 SQUARE INCHES OF FLOOD VENT AREA.
  
 PLEASE HAVE SURVEYOR REVISE ITEMS B6 AND C2(G). AN
 EMAIL HAS BEEN SENT TO CONTRACTOR AND SURVEYOR
 DETAILING ERRORS.
  
  
  
  
  
 -- FORWARDED BY SAMANTHA HILL/WESTPALM ON 10/22/2014
 04:15 PM -----
  
 FROM: SAMANTHA HILL/WESTPALM
 TO: "KEN NG" ,
 CC:
 DATE: 08/19/2014 04:08 PM
 SUBJECT: RE: PERMIT # 14071005
  
  
 IS YOUR INSTALLATION ON THE HOUSE ONLY? NOT THE
 DETACHED GARAGE?
  
 IF IT IS, THE EC IS FINE. IT HAS A MINOR ERROR WHICH I
 CAN CORRECT WITH A FORM (DON'T NEED TO HAVE THE
 SURVEYOR CHANGE THE EC). WE NEED AN ORIGINAL ALONG WITH
 THE ENGINEERING OR ICC EVALUATION REPORT FOR THE
 ENGINEERED FLOOD VENTS. TO MY KNOWLEDGE THERE IS ONLY
 ONE COMPANY MAKING FLOOD VENTS, AND THEY HAVE AN ICC
 EVALUATION REPORT (SMARTVENT). YOU'LL NEED TO DETERMINE
 THE MODEL NUMBER AND HIGHLIGHT IT FOR ME. I'LL CONFIRM
 THAT THE ENGINEERED OPENINGS COMPLY WITH THE
 REQUIREMENTS OF THE EVALUATION REPORT, AND THEN THE
 PERMIT CAN BE ISSUED. THE EC WILL BE PUT ON FILE AND
 THE STRUCTURE (HOUSE ONLY) WILL BE NOTED AS "POST
 FIRM."
  
 IF YOU'D LIKE FOR ME TO DO A PRELIMINARY REVIEW OF THE
 FLOOD VENT INFORMATION, FEEL FREE TO EMAIL THAT TO ME.
  
 IF YOU ARE DOING WORK ON THE GARAGE, I'LL NEED THAT EC
 AS WELL.
  
 THANK YOU,
  
 SAMANTHA
  
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-805-6724
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved