| 2014-09-03 14:20:26 | DATE: 9/3/2014 |
| | PROJECT: SUSHI YAMA |
| | PERMIT#: 14070978 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE COMMENTS. |
| | |
| | 1) PROVIDE POWER RISER DIAGRAM INDICATING THE LOCATION |
| | OF THE ELECTRICAL SERVICE ON THE BUILDING AND THE SIZE |
| | OF THE DISCONNECTS AND FEEDERS. |
| | |
| | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 4) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE |
| | BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE |
| | 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | 5) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR |
| | AIR CONDITIONING AND REFRIGERATION EQUIPMENT. |
| | |
| | 6) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL |
| | EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME |
| | LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. SEE NEC 210.63, |
| | 210.8(A)(3), AND 406.8(B)(1), |
| | |
| | 7) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN |
| | HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE |
| | SEQUESNCE OF EVENTS UPON ACTIVATION. |
| | |
| | 8) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| | PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD |
| | FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM, |
| | NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |