| Date |
Text |
| 2014-08-04 08:31:29 | PLUMBING PLAN REVIEW |
| | PERMIT: 14070978 |
| | ADD: 330 CLEMATIS ST #107 |
| | CONT: SCALTEC USA CORP |
| | TEL: (561)922-1888 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1STREVIEW |
| | DATE: MON. AUG. 04/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 7 SHOWS THE GREASY WASTE ISOMETRIC, PLEASE |
| | SHOW THE COMPLETE GREASY WASTE TO THE GREASE |
| | INTERCEPTOR, MISSING THE WASH UP ROOM WITH (3) |
| | COMPARTMENT SINK,SERVICE SINK, HAND SINK AND |
| | DISHWASHER. 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND |
| | AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. A GREASE |
| | INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE |
| | REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES AND |
| | EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| | PREPARATION AREAS, SUCH AS IN RESTAURANTS. FIXTURES AND |
| | EQUIPMENT SHALL INCLUDE POT SINKS, PRERINSE SINKS; SOUP |
| | KETTLES OR SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS |
| | OR SINKS INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD |
| | WASH UNITS AND DISHWASHERS WITHOUT PRERINSE |
| | SINKS.GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND |
| | EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE |
| | DISCHARGED. |
| | |
| | 2) SHEET 7 PLEASE PROVIDE THE FORMULA USED FOR SIZING |
| | OF THE EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR |
| | SHALL BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE |
| | SECTION 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW |
| | CONTROL (1003.3.4.2) OR FOR CONCRETE VAULT TYPE |
| | INTERCEPTORS (TABLE 1003.5.1). |
| | |
| | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3 |
| | COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE |
| | SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED. |
| | FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL |
| | DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED |
| | IN SECTIONS 802.1.1 THROUGH 802.1.8. |
| | |
| | 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED |
| | FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL |
| | DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN |
| | AIR GAP. |
| | |
| | 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE |
| | FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH |
| | AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE |
| | RECEPTOR IN ACCORDANCE WITH SECTION 802.2. |
| | |
| | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF |
| | UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE |
| | PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE |
| | INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR |
| | DIRECTLY CONNECT TO THE DRAINAGE SYSTEM. |
| | |
| | 4) SHEET 7 SHOWS (3) COMPARTMENT SINKS, HAND SINKS, |
| | DISHWASHER WASTE(NOT SHOWN) WITH NO TRAPS. PLEASE |
| | REVIEW 2010 FBC-P 802.2 INSTALLATION. ALL INDIRECT |
| | WASTE PIPING SHALL DISCHARGE THROUGH AN AIR GAP OR AIR |
| | BREAK INTO A WASTE RECEPTOR OR STANDPIPE. WASTE |
| | RECEPTORS AND STANDPIPES SHALL BE TRAPPED AND VENTED |
| | AND SHALL CONNECT TO THE BUILDING DRAINAGE SYSTEM. ALL |
| | INDIRECT WASTE PIPING THAT EXCEEDS 2 FEET (610 MM) IN |
| | DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 4 FEET (1219 |
| | MM) IN TOTAL DEVELOPED LENGTH, SHALL BE TRAPPED. |
| | |
| | 5) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER |
| | OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE |
| | WATER. ICE MACHINES, ICE CHEST WHICH REQUIRE INDIRECT |
| | WASTE AND COMPLIANCE TO WITH 802.1.3 POTABLE |
| | CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO THE |
| | BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| | |
| | 6) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER |
| | OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE |
| | WATER: |
| | SEE THE 2010 FBC-P: |
| | 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS. |
| | ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS |
| | INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT |
| | CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED |
| | WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF |
| | THE WATER SUPPLY SYSTEM. |
| | 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE |
| | DISPENSERS. |
| | THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND |
| | NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED |
| | AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO |
| | ASSE 1022 OR BY AN AIR GAP. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |