| 2014-08-04 09:01:02 | MECHANICAL PLAN REVIEW |
| | PERMIT: 14070978 |
| | ADD: 330 CLEMATIS ST #107 |
| | CONT: SCALTEC USA CORP |
| | TEL: (561)922-1888 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1STREVIEW |
| | DATE: MON. AUG. 04/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) NO MECHANICAL SHEETS PROVIDED, SHEET # 1 DOES HAVE |
| | MECHANICAP NOTES, SHEET # 5 NOTES 11 & 20 INDICATE A |
| | ANSUL SYSTEM AND TYPE I HOOD, NO INFORMATION AS TO MAKE |
| | UP AIR FOR THE NEW GAS APPLIANCES, ... 2010 FBC-FUEL |
| | GAS SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304S. |
| | |
| | 2) 2010 FBC-M. 420.3.14.13 SPACES HAVING EXHAUST HOODS |
| | SHALL HAVE SUFFICIENT MAKE-UP SUPPLY AIR SUCH THAT THE |
| | REQUIRED PRESSURE RELATIONSHIP WILL NOT BE AFFECTED BY |
| | THE OPERATION OF THE HOOD. 503.2.5.2.2.1 |
| | NON-RESIDENTIAL KITCHEN SPACES. |
| | NON-RESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS |
| | OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED |
| | BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING |
| | REQUIREMENTS: |
| | 1. BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR |
| | BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE |
| | PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING |
| | 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES |
| | SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING |
| | HOURS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |