| 2014-08-12 14:01:32 | DATE: 8/6/2014 |
| | PROJECT: SUSHI YAMA |
| | PERMIT#: 14070978 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. FBC 107.2.1 PLEASE PROVIDE |
| | ADDITIONAL DETAIL TO THE PLANS AS FOLLOWS: |
| | |
| | 2) PROVIDE ALLL CIRCUITRY ON THE FLOOR PLAN AND PANEL |
| | SCHEDULE, INCLUDE THE EXISTING OUTLETS, AND AS WELL AS |
| | THE NEW OUTLETS AND DISCONNECTS AS REQUIRED TO MATCH |
| | THE EQUIPMENT PLAN AS INDICATED ON SHEET 5. |
| | |
| | 3) PROVIDE POWER RISER DIAGRAM, AND THE LOCATION OF THE |
| | ELECTRICAL SERVICE ON THE BUILDING. |
| | |
| | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 6) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE |
| | BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE |
| | 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | 7) PROVIDE A LIGHTING PLAN, INDICATE ALL GENERAL |
| | PURPOSE LIGHTING TASK LIGHTING, SPECIALTY LIGHTING, |
| | SECURITY LIGHTING, EXIT AND EMERGENCY LIGHTING TO |
| | COORDINATE WITH THE LIFE SAFETY PLAN. |
| | |
| | 8) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR |
| | AIR CONDITIONING AND REFRIGERATION EQUIPMENT. |
| | |
| | 9) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL |
| | EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME |
| | LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. SEE NEC 210.63, |
| | 210.8(A)(3), AND 406.8(B)(1), |
| | |
| | 10) PROVIDE LIGHTING CONTROL. FBC-ENERGY |
| | A. 505.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| | 505.2.4. |
| | AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS |
| | LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED |
| | WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING |
| | IN THOSE AREAS. |
| | |
| | B. 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. |
| | |
| | 11) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN |
| | HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE |
| | SEQUESNCE OF EVENTS UPON ACTIVATION. WHAT IT CONTROLS |
| | AND HOW IT CONTROLS IT. |
| | |
| | 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| | PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD |
| | FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM, |
| | NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |