Plan Review Notes
Plan Review Notes For Permit 14070935
Permit Number 14070935
Review Stop E
Sequence Number 4
Notes
Date Text
2014-10-10 16:57:1110/10/2014
 PROJECT: SFRTA GENERATOR / UPS
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: NOTE
  
 1) VERIFY THE LOAD AND CIRCUIT SIZE AT EQUIPMENT RACK
 P1. THE PANEL SCHEDULE FOR PANEL UPS01 INDICATES A
 100AMP 3PHASE CIRCUIT BREAKER ON CIRCUIT #15,17,19 WITH
 A 1.75 KW LOAD. THIS APPEARS TO BE AN OVERSIGHT ONLY TO
 BE VERIFIED IN THE FIELD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  