2014-09-15 11:57:22DATE: 9/15/2014
 PROJECT: SRFTA ELECTRICAL RENNOVATION
 PERMIT#: 14070935
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E-01
 SYSTEM PHASE AND VOLTAGE IS NOT INDICATED ON THE RISER
 ANYWHERE.
 NOTE 5 CALLS FOR A 100AMP ENCLOSED CIRCUIT BREAKER BUT
 THE RISER LEADS ME TO BELIEVE THIS SHOULD BE A 400AMP
 ENCLOSED CIRCUIT BREAKER AS THE SERVICE ENTRANCE MAIN
 DISCONNECT.
 NOTE 18 CALLS FOR #2WIRE IN 1/2" CONDUIT. CLARIFICATION
 REQUIRED. INDICATE THE NUMBER AND TYPE OF WIRE
 INSTALLED, CORRECT THE CONDUIT SIZE.
 NOTE 19 CALLS FOR A 110AMP FEED WITH #2WIRE IN 1/2"
 CONDUIT. CLARIFICATION REQUIRED. INDICATE THE NUMBER
 AND TYPE OF WIRE INSTALLED, CORRECT THE CONDUIT SIZE.
 DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM
 AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR
 REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL
 BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
 PANEL SCHEDULE A THE CIRCUIT FOR UPS CALLS FOR A 3POLE
 110AMP BREAKER. HOWEVER THE CONDUIT AND WIRE SIZES
 INDICATE 6 SINGLE POLE CIRCUITS WITH 1/2" CONDUIT AND
 #12WIRE. CLARIFICATION REQUIRED.
 PANEL SCHEDULE A THE CIRCUIT FOR PANEL A-1 CALLS FOR A
 3 POLE 100AMP BREAKER. HOWEVER THE CONDUIT AND WIRE
 SIZES INDICATE 3 SINGLE POLE CIRCUITS WITH 1/2" CONDUIT
 AND #12WIRE. CLARIFICATION REQUIRED
 PANEL SCHEDULE UPS01 THE CIRCUIT FOR THE EQUIPMENT RACK
 P1 CALLS FOR A 3 POLE 100AMP BREAKER. HOWEVER THE
 CONDUIT AND WIRE SIZES INDICATE 3 SINGLE POLE CIRCUITS
 WITH 1/2" CONDUIT AND #12WIRE. CLARIFICATION REQUIRED
 PANEL SCHEDULE UPS01 THE CIRCUIT FOR THE EQUIPMENT MAIN
 BREAKER FOR UPS CALLS FOR A 3 POLE 100AMP BREAKER.
 HOWEVER THE CONDUIT AND WIRE SIZES INDICATE 3 SINGLE
 POLE CIRCUITS WITH 1/2" CONDUIT AND #12WIRE.
 CLARIFICATION REQUIRED
  
 2) SHEET E-02
 PROVIDE GROUNDING TERMINATION DETAIL. A 4/0CU GROUND
 RING IS SPECIFIED. INDICATE HOW AND WHERE THE GROUNDING
 ELECTRODE CONDUCTORS ARE TO TERMINATE TO THE GENERATOR
 AND EQUIPMENT GROUND.
  
 3) SHEET E-03
 INDICATE ON THE PLANS THE TYPE AND SIZE OF CONDUIT AND
 WIRE. INDICATE THE NUMBER OF WIRES IN EACH CONDUIT RUN
 INCLUDING HOW MANY CIRCUIT CONDUCTORS, NEUTRALS AND
 GROUNDS. THE SAME APPLIES TO THE DATA CONDUITS AND
 WIRE. INDICATE THE TYPE AND HOW MANY IN EACH.
 PROVIDE A DRAWING OF THE WIRING INSTALLATION DETAIL FOR
 THE EPO.
 PROVIDE A SCALLED DRAWING OF THE EQUIPMENT CLOSET
 INCLUDEING THE EQUIPMENT CLEARANCES REQUIRED BY THE
 MANUFACTURER OF THE UPS AND PER THE NEC 110
 PROVIDE A LOW VOLTAGE OUTLET DETAIL INDICATING WHERE
 CONDUITS ARE TO USED AND WHERE THE LOW VOLTAGE CABLE
 WILL BE INSTALLED IN FREE AIR.
 INDICATE THE CABLE INSTALLATION TYPE TO BE USED AND
 INDICATE THE ENVIRONMENT IT IS TO BE USED IN. EG:
 PLENUM AIR CEILING.
  
 4) SHEET E-04
 MAKES NO SENSE. UNNESESSARY EXCEPT FOR THE SITE PLAN
 INDICATING THE PROPOSED LOCATION OF THE GENERATOR.
 ADDITIONAL INFORMATION REQUIRED. THE GENERATOR EXHAUST
 MUST BE AT LEAST 10' AWAY FROM ANY OPERABLE WINDOWS,
 DOORS OR MECHANICAL VENTS. REVISE TO VERIFY COMPLIANCE.
  
 5) SHEET E-05
 PROVIDE A MANUFACURER'S PRODUCT APPROVAL DATA SHEET FOR
 THE RECESSED BOX FOR ELECTRIC AND COAX. MUST BE
 APPROVED FOR USE WITH HIGH AND LOW VOLTAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  