| 2014-07-24 17:45:46 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 2) SPECIFY THE SCOPE OF WORK ON THE PLANS. CITY | | | AMENDMENTS 107.2.1 | | | | | | 3) SHOW THAT THE INFILL WALL AND NEW WALL MATERIALS | | | COMPLY WITH FBC 717.5. COMBUSTIBLE MATERIALS ARE NOT | | | ALLOWED IN CONCEALED SPACES IN TYPE I OR II | | | CONSTRUCTION. | | | | | | 4) AN ELECTRICAL PERMIT WILL BE REQUIRED TO RELOCATE | | | THE SWITCH FOR THE LIGHTING OUTLET AT THE GUEST ROOM | | | WHEN THE DOOR IS MOVED. NEC 210.70 (A)(1) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|