| 2014-08-02 14:29:53 | DATE: 8/2/2014 |
| | PROJECT: THE VITAMIN SHOPPE |
| | PERMIT#: 14070799 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 THE |
| | DESIGN PROFESSIONAL IS REQUIRED TO SIGN THE PLANS. |
| | |
| | 2) IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. FBC |
| | WPB AMENDMENTS. SECTION 109.3 |
| | |
| | 3) 600.4 MARKINGS. |
| | (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND |
| | OUTLINELIGHTING SYSTEMS SHALL BE MARKED WITH THE |
| | MANUFACTURER?SNAME, TRADEMARK, OR OTHER MEANS OF |
| | IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING. |
| | (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS. |
| | SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR |
| | INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE |
| | MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE |
| | MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT |
| | LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE |
| | VISIBLE DURING RELAMPING. |
| | (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO |
| | INDICATE THAT FIELD-WIRING AND INSTALLATION |
| | INSTRUCTIONS ARE REQUIRED. |
| | NEC 110.3 LISTING AND LABELING REQUIRED BY AN APPROVED |
| | TESTING LAB. IN JUDGING EQUIPMENT, CONSIDERATION SUCH |
| | AS THE FOLLOWING SHALL BE EVALUATED: SUITABILITY FOR |
| | INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS |
| | OF THIS CODE. NEC 110.3(A)(1 THRU 8) |
| | |
| | 4) NEC 600.7(1) SIGNS AND METAL EQUIPMENT OF OUTLINE |
| | LIGHTING SYSTEMS SHALL BE GROUNDED BY CONNECTION TO THE |
| | EQUIPMENT GROUNDING CONDUCTOR OF THE SUPPLY BRANCH |
| | CIRCUIT(S) OR FEEDER USING THE TYPES OF EQUIPMENT |
| | GROUNDING CONDUCTORS SPECIFIED IN THE NEC 250.118. |
| | PROVIDE AND INDICATE ON THE PLANS THAT AN EQUIPMENT |
| | GROUNDING CONDUCTOR WILL BE ROUTED WITH THE SUPPLY |
| | CONDUCTORS AND SIZRED IN ACCORDANCE WITH THE NEC |
| | 250.118 FOR CONNECTION TO THE SIGN AS REQUIRED BY NEC |
| | 600.7 AS INDICATED ABOVE. |
| | |
| | 5) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| | 505.2.4 |
| | PROVIDE AND INDICATE ON THE PLANS HOW THE SIGN CIRCUIT |
| | WILL BE CONTROLLED IN ORDER TO MEET THE INTENT OF THE |
| | FBC-E SECTION 505.2.4 AS INDICATED ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |