| 2014-07-23 14:52:28 | DATE: 7/23/2014 |
| | PROJECT: LEASE SPACE REPAIR |
| | PERMIT#: 14070791 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. THE |
| | PLAN IS SEALED BUT NOT SIGNED. PLEASE HAVE THE PLANS |
| | SIGNED BY THE DESIGNER OF RECORD. |
| | |
| | 2) FBC-ENERGY 505.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| | 505.2.4. INDICATE LIGHTING CONTROLS FOR CODE |
| | COMPLIANCE. |
| | |
| | 3) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G) |
| | REVISE PANEL SCHEDULES TO INDICATE COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |