| 2014-08-20 14:35:34 | | | | 14070782 | | | 3300 S. DIXIE HWY #1 | | | INTERIOR RENOVATION ?THE UPS STORE? | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH | | | DISCONNECT ON THE SITE PLAN. PROVIDE AN ELECTRIC | | | SERVICE RISER PAN WHICH VERIFIES THE ELECTRICAL SERVICE | | | MAINS SERVING THIS BUILDING ARE SIX OR LESS AND GROUPED | | | IN ONE LOCATION. SHOW ALL METERS, GROUNDING, MAIN | | | DISCONNECTS AND PANEL BOARDS FOR THE BUILDING SERVICE | | | INCLUDING ALL OTHER EXISTING OCCUPANCIES REQUIRING | | | ELECTRICAL SERVICE. | | | NEC 230.2, 230.71, 230.72 | | | | | | PROVIDE A MAIN SERVICE DISCONNECT AT A READILY | | | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF | | | THE SERVICE CONDUCTORS. NEC 230.70 | | | | | | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A | | | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL | | | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | |
|