| Plan Review Notes For Permit 14070781 |
| Permit Number |
14070781 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-09-25 18:21:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLEASE REVISE THE ELEVATION CERTIFICATE IN THE | | | FOLLOWING FIELDS: | | | | | | B6, FIRM INDEX DATE, 3/1/1979 | | | B7, FIRM PANEL, 3/1/1979 | | | SECTION D, MARK BOX REGARDING LATITUDE/LONGITUDE | | | SECTION D, RAISED IMPRESSION SEAL REQUIRED | | | SECTION D, COMMENTS, INCLUDE SOURCE OF | | | LATITUDE/LONGITUDE PER INSTRUCTIONS | | | | | | 2. COMMENT FROM PREVIOUS LIST: | | | | | | BASED ON THE SPOT ELEVATIONS ON THE SURVEY, THE | | | PROPOSED IMPROVEMENT IS BELOW THE BASE FLOOD ELEVATIONS | | | AND ALL IMPROVEMENTS ARE TO BE DESIGNED TO RESIST FLOOD | | | LOADS FBC 2010 RESIDENTIAL 301. FIXTURES AND EQUIPMENT | | | ARE TO BE ABOVE BFE (7') OR TO BE FLOOD RESISTANT. GAS | | | FIXTURES ARE PROPOSED BELOW BFE. PLEASE REVISE PLAN OR | | | SUBMIT DATA WHICH DEMONSTRATES THAT PROPOSED FIXTURES | | | WILL RESIST FLOOD LOADS. | | | | | | 2ND REVIEW, I WAS UNABLE TO FIND ANYWHERE IN THE PLAN | | | THAT THE DESIGNER INCLUDES FLOOD LOADS IN DESIGN | | | CRITERIA. PLEASE REVISE PLAN. WHEN RESUBMITTING, SWAP | | | OUT SHEETS WHICH HAVE CHANGED SO THERE ARE TWO COMPLETE | | | COLLATED SETS FOR PERMIT ISSUANCE. A RESPONSE LETTER | | | INDICATING HOW THIS ITEM HAS BEEN ADDRESSED WOULD BE | | | HELPFUL. IT APPEARS THAT NEW SHEETS WERE SUBMITTED, NEW | | | INFORMATION, BUT NOT CLEAR HOW THE REQUIREMENT THAT THE | | | PROPOSED IMPROVEMENT RESIST FLOOD LOADS IF BELOW BASE | | | FLOOD ELEVATION OF 7' HAS BEEN MET. | | | | | | | | | |
|