| 2014-09-25 15:32:17 | DATE: 9/25/2014 | | | PROJECT: PARMALEE RESIDENCE | | | PERMIT#: 14070781 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) WPB AMENDMENTS TO FBC- 107.3.5.3 MINIMUM PLAN REVIEW | | | CRITERIA RESIDENTIAL; PROVIDE AN ELECTRIC SERVICE RISER | | | WITH WIRE SIZES, CONDUIT AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES, FIXTURE SCHEDULE, | | | SYMBOLS KEY LEGEND, AND INDICATE ALL CONDUIT AND WIRE | | | SIZSE FOR CIRCUITS ON SITE PLAN AND FLOOR PLAN | | | RESPECTIVELY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|