| Plan Review Notes For Permit 14070773 |
| Permit Number |
14070773 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-28 10:58:24 | DATE: 8/28/2014 | | | PROJECT: MORSE LIFE | | | PERMIT#: DATE: 8/28/2014 | | | PROJECT: MORSE LIFE | | | PERMIT#: 14070773 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) THE CIRCUIT FEEDING T-13 TO PANEL L-22 IS OVERSIZED. | | | REVISE THE OCPD AND FEEDER ACCORDINGLY. | | | | | | 2) PROVIDE THE PANEL SCHEDULES WITH LOAD CALCULATIONS | | | FOR PANEL MDP PANEL H7 AND PANEL L22 IN ORDER TO VERIFY | | | THE LOADS, CIRCUITS, OCPD'S FEEDING THE PANELS AFFECTED | | | IN THIS RENNOVATION PROJECT. | | | | | | 3) INDICATE THE LOCATIONS OF THE PANELS AFFECTED IN | | | THIS RENNOVATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|