| 2014-07-29 12:24:06 | DATE: 7/29/2014 |
| | PROJECT: 201 LINDA LANE |
| | PERMIT#: 14070769 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 THE |
| | QUALIFIER OR DESIGN PROFESSIONAL SHALL SIGN THE PLAN. |
| | |
| | 2)THIS ARTICLE PROVIDES REQUIREMENTS FOR CALCULATING |
| | BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. PART I |
| | PROVIDES FOR GENERAL REQUIREMENTS FOR CALCULATION |
| | METHODS. PART II PROVIDES CALCULATION METHODS FOR |
| | BRANCH-CIRCUIT LOADS. PARTS III AND IV PROVIDE |
| | CALCULATION METHODS FOR FEEDERS AND SERVICES. NEC 220.1 |
| | THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE |
| | LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS |
| | SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE, |
| | AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART |
| | III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. NEC |
| | 220.40 PROVIDE A LOAD CALCULATION AS REQUIRED BY NEC |
| | 220 AS NOTED ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |