Plan Review Notes
Plan Review Notes For Permit 14070769
Permit Number 14070769
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-29 12:24:06DATE: 7/29/2014
 PROJECT: 201 LINDA LANE
 PERMIT#: 14070769
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 THE
 QUALIFIER OR DESIGN PROFESSIONAL SHALL SIGN THE PLAN.
  
 2)THIS ARTICLE PROVIDES REQUIREMENTS FOR CALCULATING
 BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. PART I
 PROVIDES FOR GENERAL REQUIREMENTS FOR CALCULATION
 METHODS. PART II PROVIDES CALCULATION METHODS FOR
 BRANCH-CIRCUIT LOADS. PARTS III AND IV PROVIDE
 CALCULATION METHODS FOR FEEDERS AND SERVICES. NEC 220.1
 THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE
 LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS
 SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE,
 AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART
 III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. NEC
 220.40 PROVIDE A LOAD CALCULATION AS REQUIRED BY NEC
 220 AS NOTED ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  