| 2014-08-27 07:09:49 | ROOFING PLAN REVIEW |
| | PERMIT: 14070650 |
| | ADD: 1101 N TAMARIND AVE. |
| | CONT: FASTRACK CONSTRUCTION |
| | TEL: (561)772-8848 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. AUG. 27/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) TWO (2) ROOFING REPORTS WERE SUBMITTED ONE FOR STEEL |
| | DECKS AND ONE FOR A CONCRETE DECK, PLEASE PROVIDE THE |
| | CORRECT REPORT, CIRCLE WHICH SUB-SYSTEM WHICH IS |
| | INTENDED TO BE INSTALLED. NOTE EACH SUB-SYSTEM HAS HAS |
| | LISTED A MAXIMUM DESIGN PRESSURE, SOME HAVE A |
| | LIMITATION #7 ( ENHANCED FASTENING) OTHER HAVE A |
| | LIMITATION # 9 (MAXIMUM DESIGN PRESSURE). IF ENHANCED |
| | FASTENING IS CHOSEN A ARCHITECT OR ENGINEER MUST |
| | PROVIDE THE RAS 117 CALCULATION FOR ZONES 2 & 3 |
| | .2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR |
| | ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |