| Plan Review Notes For Permit 14070650 |
| Permit Number |
14070650 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-25 12:13:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | ON SHEET A-2 IN THE FLOOR PLAN NOTES SECTION IT READS | | | "ALL NEW DOORS SHALL BE IN FULL COMPLIANCE WITH THE | | | PROVISIONS OF NFPA 101, 24.2.4". THAT SECTION OF THE | | | CODE REFERS TO ONE AND TWO FAMILY DWELLINGS AND IS NOT | | | APPLICCABLE TO THIS OCCUPANCY. A PROVISO HAS BEEN ADDED | | | TO READ "37.2.2.2", REFERING TO MERCANTILE OCCUPANCY. | | | | | | ON SHEET A-2 IN THE FLOOR PLAN DRAWING, IT READS NEW | | | IMPACT RATED DOOR WITH SECURITY SHUTTER ON INSIDE. THE | | | SHUTTER SHALL NOT RESTRICT EGRESS AND COMPLY WITH NFPA | | | 101, CHAPTER 7. THE FIRE INSPECTOR SHALL CONFIRM | | | COMPLIANCE ON FINAL INSPECTION. |
|