| 2014-07-18 11:16:30 | DATE: 7/18/2014 | | | PROJECT: 8014FLAGLER CT. NEW POOL | | | PERMIT#: 14070638 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE | | | ELECTRICAL SERVICE ON THE HOUSE, THE FPL ELECTRICAL | | | UTILITY LINES WHETHER OVERHEAD OR UNDERGROUND AND THE | | | ELECTRICAL PANEL THAT THE POOL EQUIPMENT PANEL WILL BE | | | FED FROM AND THE AREA LIGHTING AND RECEPTACLES. FBC WPB | | | AMENDMENTS. 107.2.1, NEC 680.8, 680.10, 680.12, 680.22, | | | 680.25 | | | | | | 2) PROVIDE A RISER DIAGRAM, LOAD CALCULATION AND PANEL | | | SCHEDULE TO INDICATE THE AVAILABILITY OF CIRCUITRY AND | | | AMPACITY TO FEED THE NEW POOL EQUIPMENT. FBC WPB | | | AMENDMENTS 107.2.1, NEC 220.12, 220.14 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND | | | LEAVE THE PREVIOUSLY REVIEWED SHEETS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|