Plan Review Notes
Plan Review Notes For Permit 14070638
Permit Number 14070638
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-18 18:00:58APPROVED WITH EXCEPTIONS. SEE NOTES ON THE PLANS.
 - STRUCTURAL ENGINEER IS TO SUBMIT TWO SETS OF SIGNED
 AND SEALED STRUCTURAL DETAILS OF THE REINFORCED POOL
 FLOOR SPECIFYING THE THICKNESS AND PSI OF THE CONCRETE.
 - THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE. THE
 EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE REQUIRED
 MINIMUM BASE FLOOD ELEVATION OF 7.5'.
 - A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE AUGER PILINGS.
 - A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE GAS PIPING SUPPLYING THE POOL HEATER.