Plan Review Notes
Plan Review Notes For Permit 14070624
Permit Number 14070624
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-23 09:06:04DATE: 7/23/2014
 PROJECT: 831 43RD ST
 PERMIT#: 14070624
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE
 SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), OR AT A SEPARATELY
 DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM
 SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, NEC
 250.66 #6 MINIMUM IS REQUIRED.
  
 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 3) VI. SERVICE EQUIPMENT DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE
 CONDUCTORS. (A) LOCATION. THE SERVICE DISCONNECTING
 MEANS SHALL BE INSTALLED IN ACCORDANCE WITH
 230.70(A)(1), (A)(2), AND (A)(3). (1) READILY
 ACCESSIBLE LOCATION. THE SERVICE DISCONNECTING MEANS
 SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION
 EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE
 NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS. NEC 230.70 THE PLAN INDICATES THE MAIN
 LOCATED IN THE PANEL BUT THE LOCATION OF THE PANEL IS
 NOT IDENTIFIED.
 PROVIDE MAIN DISCONNECT IN COMPLIANCE WITH THE
 PROVISIONS OF NEC 230.70 AS DEFINED ABOVE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved