| 2014-07-23 08:07:19 | DATE: 7/23/2014 | | | PROJECT: | | | PERMIT#: | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | ADDITIONAL INFORMATION IS REQUIRED. PLEASE PROVIDE THE | | | FOLLOWING: | | | 1) A SINGLE LINE DIAGRAM. | | | 2) A LOAD CALCULATION OR A YEARS WORTH OF LOAD READINGS | | | FORM THE LOCAL UTILITY. | | | 3) THE SYSTEM VOLTAGE, AMPERAGE AND WIRE SIZE. | | | 4) THE BRAND NAME OF THE GENERATOR. WITH A CUT SHEET | | | LISTING APPROVED BREAKERS. | | | 5) THE BRAND NAME SIZE AND TYPE OF THE BREAKER TO BE | | | REPLACED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND | | | LEAVE THE PREVIOUSLY REVIEWED SHEETS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|