| 2014-07-18 09:40:32 | DATE: 7/18/2014 |
| | PROJECT: PBL MALL F-5 |
| | PERMIT#: 14050005 REVISION# 14070608 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) BREAKER, CONDUIT AND WIRE SIZE FEEDING THE 45KW |
| | TRANSFORMER FROM PANEL "H" ARE ALL UNDERSIZED. NEC |
| | 240.6, 310.16 |
| | |
| | 2) WIRE SIZE FROM 45KW TRANSFORMER FEEDING PANEL "L" IS |
| | UNDERSIZED FOR THE LOAD TO BE SERVED. NEC310.16 |
| | |
| | 3) AN EQUIPMENT GROUND WIRE IS REQUIRED FROM PANEL "H" |
| | TO THE 45KW TRANSFORMER. NEC 250.110 |
| | |
| | 4) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. THEREFORE |
| | THE SIGN TO BE CIRDUITED THROUGH ASTROMONMICAL TIMER OR |
| | PHOTOSENSOR. FBC-ENERGY 505.2.4 EXTERIOR LIGHTING |
| | CONTROLS. |
| | |
| | 5) FBC-ENERGY 505.2 LIGHTING CONTROLS (MANDATORY). |
| | STATES. LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| | CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| | 505.2.3 AND 505.2.4. THEREFORE A LIGHTING CONTROL |
| | SYSTEM IN COMPLIANCE WITH THE ABOVE REFERENCED CODE |
| | SHALL BE PROVIDED AND INDICATED ON THE PLANS. |
| | |
| | 6) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. THANK YOU. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |