Plan Review Notes
Plan Review Notes For Permit 14070599
Permit Number 14070599
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2014-12-12 17:06:40290 COURTNEY LAKES CIRCLE
 TRACKING #14070599
 PERMIT #13060771
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE DOOR SCHEDULE OF SHEET A7.01 INDICATES THAT DOORS
 #7-101 ARE EQUIPPED WITH PANIC HARDWARE; HOWEVER, SHEET
 A0.05 INDICATES THE DOORS ARE TO BE EQUIPPED WITH AN
 ADAMSRITE LOCK INDICATOR FOR KEY OPERATED DOOR LOCKS. A
 PREVIOUSLY ISSUED PERMIT INDICATES MAGNETIC LOCKS ON
 THESE DOORS AS WELL.
  
 REPEAT COMMENT:
 FIRE INSPECTOR IN THE FIELD HAS INDICATED THAT ALL
 CLUBHOUSE EXIT DOORS ARE ALREADY EQUIPPED WITH MAGNETIC
 LOCKING DEVICES (PERMIT #14090532 SHEET LV1.01). DESIGN
 TEAM AND CONTRACTOR(S) NEED TO START COMMUNICATING AND
 COORDINATING WHAT DOOR HARDWARE IS TO BE INSTALLED ON
 ALL/EACH EXIT DOOR. IT IS VERY UNCLEAR WHAT
 LOCKS/LATCHES/HARDWARE ARE INTENDED (MAGNETIC LOCKS,
 KEY-OPERATED LOCKS, PANIC HARDWARE, ETC.).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE