| 2014-10-17 11:11:39 | BUILDING PLAN REVIEW |
| | REVISION: 14070599 |
| | PERMIT: 13051012 |
| | ADD: 290 COURTNEY LAKES |
| | CONT:KAST |
| | TEL: (561) 856-6655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT 17/2014 |
| | ACTION: DENIED |
| | |
| | 1) MASTER # 13060771 REVSION 6 - PANIC HARDWARE REMOVED |
| | FROM CLUBHOUSE ENTRY DOOR. PLEASE SEE CODE SECTION 2010 |
| | FBC-B 1008.1.9.3 & EXCEPTION # 2. |
| | 1A) IN THE BEGINNING OF EXCEPTION # 2. THE ONLY DOORS |
| | THAT THIS EXCEPTION APPLIES TO IS THE MAIN EXTERIOR |
| | DOORS. |
| | |
| | 2010 FBC-B 1008.1.9.3 & EXCEPTION # 2. IN BUILDINGS IN |
| | OCCUPANCY GROUP A HAVING AN OCCUPANT LOAD OF 300 OR |
| | LESS, GROUPS B, F, M AND S, AND IN PLACES OF RELIGIOUS |
| | WORSHIP, THE MAIN EXTERIOR DOOR OR DOORS ARE PERMITTED |
| | TO BE EQUIPPED WITH KEY-OPERATED LOCKING DEVICES FROM |
| | THE EGRESS SIDE PROVIDED: |
| | |
| | THE DESIGNER OF RECORD HAS NOT DESIGNATED WHICH DOOR OR |
| | SET OF DOORS IS TO BE CONSIDERED THE MAIN ENTRY WHERE |
| | THE PANIC HARDWARE CAN BE ELIMINATED. ALL OTHER |
| | REQUIRED EXIT DOORS WILL REQUIRE TO HAVE PANIC HARDWARE |
| | AS REQUIRED IN SECTION 1008.1.10. SHEET A0.05 AND THE |
| | DOOR SCHEDULE WILL NEED TO BE UPDATED TO REFLECT THE |
| | CHANGES IN HARDWARE. |
| | |
| | 1B) IN SECTION: 1008.19.3 EXCEPTION # 2: SECTION 2.2. A |
| | READILY VISIBLE DURABLE SIGN IS POSTED ON THE EGRESS |
| | SIDE ON OR ADJACENT TO THE DOOR STATING: THIS DOOR TO |
| | REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE SIGN |
| | SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A |
| | CONTRASTING BACKGROUND; |
| | THIS PART OF THE REQUIRED CODE REQUIREMENT HAS NOT BEEN |
| | MENTION NOR DISPLAYED AS PART OF THE EXCEPTION. |
| | |
| | 1C) THE MANUFACTURERS SPEC ON THE LOCK INDICATES THAT |
| | IT IS NOT A LOCKING TYPE AND WILL MEET THE REQUIREMENTS |
| | OF 2.3. |
| | |
| | PLEASE NOTE THE 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 102.4 |
| | REFERENCED CODES AND STANDARDS. WHERE DIFFERENCES OCCUR |
| | BETWEEN PROVISIONS OF THIS CODE MOST STRIGENT CODE |
| | SHALL APPLY. THE FIRE CODES MAY HAVE BE THE MORE |
| | STRIGENT OF THE (2) CODES AND THEN GOVERN. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |