| Plan Review Notes For Permit 14070599 |
| Permit Number |
14070599 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-23 14:45:35 | 290 COURTNEY LAKES CIRCLE | | | TRACKING #14070599 | | | PERMIT #13060771 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE REMOVING PANIC HARDWARE FROM THE | | | MAIN ENTRANCE DOUBLE DOORS; HOWEVER, THE OCCUPANT LOAD | | | UTILIZING THESE DOORS APPEARS TO BE GREATER THAN 50 | | | PERSONS. THE TWO CONFERENCE ROOMS AND THE BREAK ROOM | | | SHOULD BE CALCULATED USING AN OCCUPANT LOAD FACTOR OF | | | 15 SQ.FT. PER PERSON AS THESE ARE ASSEMBLY USE SPACES. | | | THESE SPACES CAN BE CONSIDERED PART OF THE BUSINESS | | | OCCUPANCY BECAUSE THEIR INDIVIDUAL USES ARE LESS THAN | | | 50 PERSONS BUT THEIR OCCUPANT LOAD FACTORS WOULD STILL | | | BE 15 SQ.FT. PER PERSON. ADDING THESE INCREASED | | | OCCUPANCY LOADS TO THE 30 OCCUPANTS FROM THE CLUB ROOM | | | RESULTS IN AN OCCUPANT LOAD GREATER THAN 50 PERSONS AND | | | WOULD REQUIRE PANIC HARDWARE ON THE MAIN ENTRY DOOR(S). | | | | | | THE SECONDARY EXIT FROM THE CLUB ROOM IS NOW SHOWN | | | EXITING THROUGH THE PARTY/CAFE ROOM. THIS WILL RESULT | | | IN A POSSIBLE OCCUPANT LOAD OF GREATER THAN 50 PERSONS | | | (25+30) UTILIZING THE EXIT DOOR IN THE PARTY/CAFE ROOM | | | AND THERE DOES NOT APPEAR TO BE PANIC HARDWARE ON THIS | | | DOOR. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|