Plan Review Notes
Plan Review Notes For Permit 14070599
Permit Number 14070599
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-09-23 14:45:35290 COURTNEY LAKES CIRCLE
 TRACKING #14070599
 PERMIT #13060771
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE REMOVING PANIC HARDWARE FROM THE
 MAIN ENTRANCE DOUBLE DOORS; HOWEVER, THE OCCUPANT LOAD
 UTILIZING THESE DOORS APPEARS TO BE GREATER THAN 50
 PERSONS. THE TWO CONFERENCE ROOMS AND THE BREAK ROOM
 SHOULD BE CALCULATED USING AN OCCUPANT LOAD FACTOR OF
 15 SQ.FT. PER PERSON AS THESE ARE ASSEMBLY USE SPACES.
 THESE SPACES CAN BE CONSIDERED PART OF THE BUSINESS
 OCCUPANCY BECAUSE THEIR INDIVIDUAL USES ARE LESS THAN
 50 PERSONS BUT THEIR OCCUPANT LOAD FACTORS WOULD STILL
 BE 15 SQ.FT. PER PERSON. ADDING THESE INCREASED
 OCCUPANCY LOADS TO THE 30 OCCUPANTS FROM THE CLUB ROOM
 RESULTS IN AN OCCUPANT LOAD GREATER THAN 50 PERSONS AND
 WOULD REQUIRE PANIC HARDWARE ON THE MAIN ENTRY DOOR(S).
  
 THE SECONDARY EXIT FROM THE CLUB ROOM IS NOW SHOWN
 EXITING THROUGH THE PARTY/CAFE ROOM. THIS WILL RESULT
 IN A POSSIBLE OCCUPANT LOAD OF GREATER THAN 50 PERSONS
 (25+30) UTILIZING THE EXIT DOOR IN THE PARTY/CAFE ROOM
 AND THERE DOES NOT APPEAR TO BE PANIC HARDWARE ON THIS
 DOOR.
  