Plan Review Notes
Plan Review Notes For Permit 14070567
Permit Number 14070567
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-29 11:41:591ST REVIEW: 2010 FBC
 THE FOLLOWING DEFICIENTCIES ARE NOTED
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, DOORS, SKYLIGHT,
 LOUVERS, ECT SUBMITTALS.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16, CITE THE CODE IN
 EFFECT. PROVIDE CLARIFICATION AS TO THE FASTENERS FOR
 HURRUCANE STRAPS AND NAIL TYPE FOR SHEATHING, (RING
 SHANK)
  
 FBC 1209.2 SHOW DETAILS FOR PROVIDING ATTIC ACCESS.
  
 FBC 1803.2 PROVIDE GEOTECHNICAL SOIL INVESTIGATION.
 SOIL RECOMMENDATIONS AND REQUIRED SOIL BEARING
 CAPACITY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  
  
  
  