Plan Review Notes
Plan Review Notes For Permit 14070541
Permit Number 14070541
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-06 08:19:11DATE: 8/6/2014
 PROJECT: 1701 S. FLAGLER DR. #307
 PERMIT#: 14070541
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO.
  
 1) 250.86 OTHER CONDUCTOR ENCLOSURES AND RACEWAYS.
 EXCEPT AS PERMITTED BY 250.112(I), METAL ENCLOSURES AND
 RACEWAYS FOR OTHER THAN SERVICE CONDUCTORS SHALL BE
 CONNECTED TO THE EQUIPMENT GROUNDING CONDUCTOR. IF NO
 EQUIPMENT GROUND IS AVAILABLE OR PROPOSED TO BE
 INSTALLED, THEN PLEASE INDICATE COMPLIANCE WITH THE
 FOLLOWING ARTICLE FROM THE 2008 EDITION OF THE NEC
 250.96 SEE BELOW:
  
 2) NEC 250.96 BONDING OTHER ENCLOSURES. (A) GENERAL.
 METAL RACEWAYS, CABLE TRAYS, CABLE ARMOR, CABLE SHEATH,
 ENCLOSURES, FRAMES, FITTINGS, AND OTHER METAL
 NON?CURRENT-CARRYING PARTS THAT ARE TO SERVE AS
 GROUNDING CONDUCTORS, WITH OR WITHOUT THE USE OF
 SUPPLEMENTARY EQUIPMENT GROUNDING CONDUCTORS, SHALL BE
 BONDED WHERE NECESSARY TO ENSURE ELECTRICAL CONTINUITY
 AND THE CAPACITY TO CONDUCT SAFELY ANY FAULT CURRENT
 LIKELY TO BE IMPOSED ON THEM. ANY NONCONDUCTIVE PAINT,
 ENAMEL, OR SIMILAR COATING SHALL BE REMOVED AT THREADS,
 CONTACT POINTS, AND CONTACT SURFACES OR BE CONNECTED BY
 MEANS OF FITTINGS DESIGNED SO AS TO MAKE SUCH REMOVAL
 UNNECESSARY.
  
 3) THE PLAN INDICATES REPLACEMENT OF AN FPE LOADCENTER
 BUT DOESN'T INDICATE WHAT IT WILL BE REPLACED WITH.
 INDICATE COMPLIANCE WITH THE FOLLOWING:
 408.36 OVERCURRENT PROTECTION. IN ADDITION TO THE
 REQUIREMENT OF 408.30, A PANELBOARD SHALL BE PROTECTED
 BY AN OVERCURRENT PROTECTIVE DEVICE HAVING A RATING NOT
 GREATER THAN THAT OF THE PANELBOARD. THIS OVERCURRENT
 PROTECTIVE DEVICE SHALL BE LOCATED WITHIN OR AT ANY
 POINT ON THE SUPPLY SIDE OF THE PANELBOARD. INDICATE
 THE RATING TYPE AND STYLE OF THE NEW PANELBOARD.
  
 4) THE FBC-RESIDENTIAL STATES THE FOLLOWING: WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314.3 AND
 314.3.1 PLEASE INDICATE COMPLIANCE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]