| 2014-11-06 14:22:09 | 11/6/2014 |
| | PROJECT: ZOECKLER |
| | PERMIT#: 14070538 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. NEC 210.11(C)(3) REVISE PANEL |
| | SCHEDULE AND ELECTRICAL FLOOR PLAN TO INDICATE THE |
| | REQUIRED 20AMP BRANCH CIRCUIT FOR THE BATHROOMS. |
| | |
| | 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET. NEC 210.52 (A)(1) REVISE ELECTRICAL FLOOR PLAN |
| | TO COMPLY WITH 210.52 |
| | |
| | 3) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. NEC210.52(C)(1) REVISE ELECTRICAL FLOOR PLAN TO |
| | COMPLY WITH 210.52 |
| | |
| | 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. NEC 210.8(A) (1) |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |