| Plan Review Notes For Permit 14070538 |
| Permit Number |
14070538 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-06 09:38:11 | PLAN REVIEW COMMENTS | | | | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | MECHANICAL | | | | | | 1) THE MECHANICAL PLANS ARE SHOWN ON THE ELECTRICAL | | | PLANS ON SHEET 5 OF 7. PLEASE PROVIDE A SEPARATE | | | MECHANICAL DRAWING OR LABEL THIS DRAWING ELECTRICAL / | | | MECHANICAL PLANS. FBC 107.2.1.4 | | | | | | 2) SPECIFY THE SIZE OF THE RETURN AIR DUCTS AND GRILLS | | | THAT ARE SHOWN ON THE PLANS. FBC 107.3.5.1.4 | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN | | | WITH THE MODEL NUMBERS AND SPECIFICATIONS OF THE | | | EQUIPMENT. THE MECHANICAL EQUIPMENT SPECIFIED SHALL BE | | | CONSISTENT WITH HVAC LOAD SIZING CALCULATIONS. FBC | | | 107.2.1 | | | |
|