| 2014-10-06 16:48:09 | 10/6/2014 |
| | PROJECT: ZOECKLER |
| | PERMIT#: 14070538 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | 1) NEC 215.2 MINIMUM RATING AND SIZE. (A) FEEDERS NOT |
| | MORE THAN 600 VOLTS. (1) GENERAL. FEEDER CONDUCTORS |
| | SHALL HAVE AN AMPACITY NOT LESS THAN REQUIRED TO SUPPLY |
| | THE LOAD AS CALCULATED IN PARTS III, IV, AND V OF |
| | ARTICLE 220. THE MINIMUM FEEDER-CIRCUIT CONDUCTOR SIZE, |
| | BEFORE THE APPLICATION OF ANY ADJUSTMENT OR CORRECTION |
| | FACTORS, SHALL HAVE AN ALLOWABLE AMPACITY NOT LESS THAN |
| | THE NONCONTINUOUS LOAD PLUS 125 PERCENT OF THE |
| | CONTINUOUS LOAD.THE ELECTRICAL RISER DIAGRAM TO BE |
| | REVISED TO INDICATE THE CORRECT WIRE SIZES TO SUPPORT |
| | THE TOTAL CONNECTED LOAD TO BE SERVED. |
| | |
| | 2) NEC 220.40 GENERAL. THE CALCULATED LOAD OF A FEEDER |
| | OR SERVICE SHALL NOT BE LESS THAN THE SUM OF THE LOADS |
| | ON THE BRANCH CIRCUITS SUPPLIED, AS DETERMINED BY PART |
| | II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND FACTORS |
| | PERMITTED BY PART III OR IV OR REQUIRED BY PART V HAVE |
| | BEEN APPLIED. THE LOAD CALCULATION SHALL BE RIVISED TO |
| | INDICATE A TOTAL CALCULATED LOAD AS DIRECTED BY ARTICLE |
| | 220 IN THE NEC. |
| | |
| | 3) NEC 408.4 EVERY CIRCUIT AND CIRCUIT MODIFICATION |
| | SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, |
| | AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT |
| | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE |
| | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| | PANELBOARD, AND LOCATED AT EACH SWITCH ON A |
| | SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER |
| | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
| | |
| | 4) FBC-RESIDENTIAL 314 AND 315. WHEN ALTERATIONS, |
| | REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| | ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| | EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| | BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| | NEW DWELLINGS. SMOKE AND CARBON MONOXIDE DETECTORS ARE |
| | ONLY REQUIRED INSIDE AND OUTSIDE OF SLEEPING AREAS AS |
| | DIRRECTED BY THE FBC 314-315. REVISE PLANS ACCORDINGLY. |
| | |
| | 5) NEC 410.16(A) AND (B) LUMINAIRES IN CLOTHES CLOSETS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF |
| | THE NEC 410.16(A) AND (B). REVISE PLANS TO INDICATE |
| | REQUIRED CLEARANCES. |
| | |
| | 6) NEC 314(B)(C)&(D) FOR OUTLET BOXES OR OUTLET BOX |
| | SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) |
| | FANS THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. (D) BOXES AT CEILING-SUSPENDED (PADDLE) FAN |
| | OUTLETS. NOTE PLANS ACCORDINGLY AT CEILING FAN OUTLET |
| | LOCATIONS. |
| | |
| | 7) FBC 713.3.2 MEMBRANE PENETRATIONS. |
| | MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION |
| | 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE |
| | A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL |
| | NOT BE REDUCED. |
| | FBC R302.4.2 MEMBRANE PENETRATIONS. |
| | MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION |
| | R302.4.1. WHERE WALLS ARE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| | INSTALLED SO THAT THE REQUIRED FIRE-RESISTANCE RATING |
| | WILL NOT BE REDUCED. INDICATE AND CLARIFY HOW THE FIRE |
| | RATING WILL BE MAINTAINED BETWEEN DWELLING UNITS AT ALL |
| | BACK TO BACK ELECTRICAL DEVICE OPENINGS. |
| | |
| | 8) CLARIFY THE 220V DEVICE INDICATED UNDER THE SINK. |
| | |
| | 9) CLAIRIFY INDICATE AND MAINTAIN A MINIMUM 3' |
| | CLEARANCE BETWEEN SMAOKE DETECTORS AND A/C DIFUSERS AND |
| | CEILING FANS. |
| | |
| | 10) THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE |
| | DISCONNECTING MEANS CAPABLE OF DISCONNECTING |
| | AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING |
| | MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT |
| | CONDUCTORS. NEC 440.11 PROVIDE AND INDIACTE DISCONNECTS |
| | WHERE REQUIRED FOR A/C CONDENSING UNITS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |