| Plan Review Notes For Permit 14070538 |
| Permit Number |
14070538 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-06 10:19:48 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | MECHANICAL | | | | | | 1) FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION | | | | | | 2) FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | | M15. | | | | | | 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | | | 4) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. | | | | | | 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | | SPECIFICATIONS OF THE EQUIPMENT IN AN EQUIPMENT | | | SCHEDULE ON THE MECHANICAL PLAN THAT CORRESPONDS WITH | | | THE EQUIPMENT SIZING CALCULATIONS. | | 2014-08-20 13:48:18 | PROVIDE ENERGY FORMS FOR TOTAL STRUCTURE | | | PROVIDE DUCT LAYOUT AND EQUIPMENT USED |
|