| Plan Review Notes For Permit 14070510 |
| Permit Number |
14070510 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-29 18:22:04 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) SEVERAL OF THE ELECTRICAL LOAD CALCULATIONS ON SHEET | | | E3.0 ARE LABELED WITH INCORRECT UNIT LETTERS. UNIT "C" | | | (1613 SF) IS LABELED AS UNIT "B". UNIT "D" (1681 SF) IS | | | LABELED AS UNIT "C". UNIT "F" (1765 SF) IS LABELED AS | | | UNIT "C". PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | | | 2) THE ELECTRIC SERVICE CALCULATION FOR UNIT "D" HAS 10 | | | KW LISTED FOR THE AHU / HEAT STRIP AND IT SHOULD BE 8 | | | KW. PLEASE CORRECT AND ADJUST THE TOTAL. NEC 220 | | | | | | IN ORDER TO AVOID DELAYS IN PERMITTING PLEASE DOUBLE | | | CHECK PLANS BEFORE RE-SUBMITTING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|