2014-07-29 18:22:042010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SEVERAL OF THE ELECTRICAL LOAD CALCULATIONS ON SHEET
 E3.0 ARE LABELED WITH INCORRECT UNIT LETTERS. UNIT "C"
 (1613 SF) IS LABELED AS UNIT "B". UNIT "D" (1681 SF) IS
 LABELED AS UNIT "C". UNIT "F" (1765 SF) IS LABELED AS
 UNIT "C". PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 2) THE ELECTRIC SERVICE CALCULATION FOR UNIT "D" HAS 10
 KW LISTED FOR THE AHU / HEAT STRIP AND IT SHOULD BE 8
 KW. PLEASE CORRECT AND ADJUST THE TOTAL. NEC 220
  
 IN ORDER TO AVOID DELAYS IN PERMITTING PLEASE DOUBLE
 CHECK PLANS BEFORE RE-SUBMITTING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW