2014-07-19 12:15:042010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) THE LOAD CALCULATIONS FOR UNIT B ON SHEET E3.0
 CONTAINS A NUMBER OF MISTAKES. PLEASE REVIEW AND MAKE
 CORRECTIONS. NEC 220
  
 2) ON SHEET E3.0 A #8 WIRE IS SPECIFIED FOR THE 10 KW
 HEAT STRIP WITH A 2 POLE / 60 AMP BREAKER IN THE PANEL
 SCHEDULE FOR UNIT A. A #6 WIRE IS REQUIRED FOR THIS
 APPLICATION. PLEASE CORRECT. NEC TABLE 316.16.
  
 3) PER THE MECHANICAL EQUIPMENT SCHEDULE UNITS B, C AND
 D HAVE 8 KW HEAT STRIPS WITH MAXIMUM 45 AMP
 OVER-CURRENT PROTECTION AND UNITS A AND F HAVE 10 KW
 HEAT STRIPS WITH MAXIMUM 60 AMP OVER-CURRENT
 PROTECTION. PLEASE REVIEW. CITY AMENDMENTS 107.2.1
  
 4) ON SHEET E1.0 THE LOCATION OF THE ELECTRICAL PANEL
 AND THE WATER HEATER IN THE GARAGE OF UNIT D WILL NEED
 TO BE COORDINATED SO THAT THE DEDICATED WORKING SPACE
 IN FRONT OF THE ELECTRICAL PANEL REQUIRED BY NEC 110.26
 IS PROVIDED.
  