| 2014-07-19 12:15:04 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) THE LOAD CALCULATIONS FOR UNIT B ON SHEET E3.0 | | | CONTAINS A NUMBER OF MISTAKES. PLEASE REVIEW AND MAKE | | | CORRECTIONS. NEC 220 | | | | | | 2) ON SHEET E3.0 A #8 WIRE IS SPECIFIED FOR THE 10 KW | | | HEAT STRIP WITH A 2 POLE / 60 AMP BREAKER IN THE PANEL | | | SCHEDULE FOR UNIT A. A #6 WIRE IS REQUIRED FOR THIS | | | APPLICATION. PLEASE CORRECT. NEC TABLE 316.16. | | | | | | 3) PER THE MECHANICAL EQUIPMENT SCHEDULE UNITS B, C AND | | | D HAVE 8 KW HEAT STRIPS WITH MAXIMUM 45 AMP | | | OVER-CURRENT PROTECTION AND UNITS A AND F HAVE 10 KW | | | HEAT STRIPS WITH MAXIMUM 60 AMP OVER-CURRENT | | | PROTECTION. PLEASE REVIEW. CITY AMENDMENTS 107.2.1 | | | | | | 4) ON SHEET E1.0 THE LOCATION OF THE ELECTRICAL PANEL | | | AND THE WATER HEATER IN THE GARAGE OF UNIT D WILL NEED | | | TO BE COORDINATED SO THAT THE DEDICATED WORKING SPACE | | | IN FRONT OF THE ELECTRICAL PANEL REQUIRED BY NEC 110.26 | | | IS PROVIDED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|