| Plan Review Notes For Permit 14070494 |
| Permit Number |
14070494 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-29 10:52:52 | WPB ADMIN. AMEND. TO 2010 FBC. 107.2.1. | | | 1) PROVIDE A SANITARY RISER FOR THE SECOND FLOOR | | | BATHROOM. | | | 2) SIZE ALL SECTIONS OF THE SANITARY RISER (HORIZONTAL | | | & VERTICAL) | | | 3) LAUNDRY TRAY IN GARAGE IS NOT VENTED. 2010FBCR | | | SEC.P3105.1 | | | 4) THE AAV IS NOT REQUIRED ON THE DOUBLE LAVS SINCE | | | THERE IS A VENT THRU THE ROOF. | | | 5) THE MINIMUM SIZE DRAIN FOR THE WASHING MACHINE SHALL | | | BE 2 " PER TABLE P3201.7 OF THE 2010 FBCR. THE | | | STANDPIPE SHALL COMPLY W/ SEC.P 2706.2. | | | 6) THE LAYOUT OF THE RISER AS DRAWN DOES NOT CORRELATE | | | WITH THE FLOOR PLAN. | | | 7) THE SHOWER COMPARTMENT ACCESS AND EGRESS OPENING | | | SHALL HAVE A MINIMUM CLEAR AND UNOBSTRUCTED FINISHED | | | WIDTH OF 22 INCHES PER 2010 FBCR SEC.P2708.1.1. | | | 8) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKSPER | | | 2010FBCR SEC.3005.2.6. ( SEE EXCEPTIONS). |
|