| Plan Review Notes For Permit 14070459 |
| Permit Number |
14070459 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-24 13:31:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISE FLOOR PLAN TO PROVIDE ROOM DESIGNATIONS , FBC | | | 2010 RESIDENTIAL 310, EXISTING BUILDING 604.1. | | | | | | 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING | | | INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE | | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%: | | | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | | MANUFACTURER | | | | | | 3. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED, | | | FAC9N-3. THERE WERE NO PRODUCT APROVALS IN THE PERMIT | | | SUBMITTAL PACKAGE. | | | | | | | | | |
|