Plan Review Notes
Plan Review Notes For Permit 14070459
Permit Number 14070459
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-24 13:31:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO PROVIDE ROOM DESIGNATIONS , FBC
 2010 RESIDENTIAL 310, EXISTING BUILDING 604.1.
  
 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED,
 FAC9N-3. THERE WERE NO PRODUCT APROVALS IN THE PERMIT
 SUBMITTAL PACKAGE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved