| 2014-07-21 13:14:57 | DATE: 7/21/2014 |
| | PROJECT: |
| | PERMIT#: |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND |
| | APPLICATION INDICATE COMPLETE REWIRING CONFORMING TO |
| | ALL CURRENT FBC AND NEC BUT THE FLOORPLAN LAYOUT DO NOT |
| | CONFORM TO CODE. RE-SUBMIT WITH THE ACTUAL LOCATIONS OF |
| | THE ELECTRICAL SERVICE THE MAIN DISCONNECTING MEANS, |
| | THE ELECTRICAL PANEL, AS WELL AS ALL SWITCHES AND |
| | OUTLETS AS REQUIRED BY NEC 210.52, SMOKE DETETCTORS, |
| | A/C EQUIPMENT APPLIANCES, WASHER DRYER WATER HEATER, |
| | AND ANY AND ALL ELECTRICAL UTILITY DEVICES AND |
| | EQUIPMENT TO BE INSTALLED. FBC 170.2.1 |
| | |
| | 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| | STRUCTURES. NEC 250.94. |
| | |
| | 3) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A |
| | BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF |
| | ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1) |
| | |
| | 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 A FAULT CURRENT ALCULATION IS |
| | REQUIRED. |
| | |
| | 5) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT |
| | BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| | CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD |
| | CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 |
| | |
| | 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | |
| | 7) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | 8) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| | BATHROOMS. NEC 210.11 (C) |
| | |
| | 9) ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 |
| | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 |
| | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| | |
| | 10) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | 11) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| | LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| | SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| | CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| | KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| | DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. NEC 314(D) BOXES AT CEILING-SUSPENDED |
| | (PADDLE) FAN OUTLETS. |
| | |
| | 12) AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED |
| | FOR EACH CONTROLLER AND SHALL DISCONNECT THE |
| | CONTROLLER. THE DISCONNECTING MEANS SHALL BE LOCATED IN |
| | SIGHT FROM THE CONTROLLER LOCATION NEC 430.102 |
| | LOCATION. |
| | |
| | 13) EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO |
| | INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE |
| | PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT |
| | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. NEC |
| | 110.22 (A) |
| | |
| | THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT |
| | OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION |
| | DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL |
| | CURRENT CODES AND ORDINCES PLEASE READ AND AND COMPLY |
| | WITH THE PROVISIONS OF THE 2008 EDITION OF THE NATIONAL |
| | ELECTRICAL CODE, AND THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE AS WELL AS THE WEST PALM BEACH AMENDMENST |
| | TO CHAPTER ONE OF THE FLORIDA BUILDING CODE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |