| 2014-07-15 08:31:47 | DATE: 7/14/2014 |
| | PROJECT: REWIRE DUPLEX |
| | PERMIT#: 14070442 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) IDENTIFY CIRCUITRY ON FLOOR PLAN. FBC 107.2.1 |
| | |
| | 2) PROVIDE PANEL SCHEDULE FOR EACH APT. FBC 107.2.1 |
| | |
| | 3) PROVIDE REVISED LOAD CALCULATION TO INCLUDE 2 |
| | KITCHEN APPLIANCE CIRCUITS FOR EACH DWELLING UNIT AND |
| | TOTAL SQUARE FOOTAGE OF BOTH UNITS. NEC 220. FEEDER |
| | CONDUCTORS SHALL HAVE AN AMPACITY NOT |
| | LESS THAN REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN |
| | PARTS III, IV, AND V OF ARTICLE 220. THE MINIMUM |
| | FEEDER-CIRCUIT CONDUCTOR SIZE, BEFORE THE APPLICATION |
| | OF ANY ADJUSTMENT OR CORRECTION FACTORS, SHALL HAVE AN |
| | ALLOWABLE AMPACITY NOT LESS THAN THE NONCONTINUOUS LOAD |
| | PLUS 125 PERCENT OF THE CONTINUOUS LOAD. |
| | |
| | 4) PROVIDE REVISED RISER DIAGRAM TO INDICATE THE ACTUAL |
| | INSATLLATION PROPOSED. IDENTIFY EACH METER WITH THE |
| | CORRECT ADDRESS AND EACH MAIN WITH THE UNIT # IT FEEDS. |
| | INDICATE ON THE RISER THE LOCATION OF THE LOAD CENTERS. |
| | NEC 215.5 |
| | |
| | 5) BACK TO BACK OUTLETS BETWEEN APTS. TO BE FIRE RATED. |
| | |
| | 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | |
| | 7) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | 8) GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND |
| | REAR ELEVATIONS. NEC 210.8 |
| | |
| | 9) PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE |
| | BRANCH CIRCUITS. NEC 210.52 |
| | |
| | 10) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| | BATHROOMS. NEC 210.11 (C)(3) |
| | |
| | 11) A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE |
| | GROUND NEC 250.94 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WPCONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBMI |
| | TTAL_FORM_04132010.PDF. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |