Plan Review Notes
Plan Review Notes For Permit 14070420
Permit Number 14070420
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-21 11:07:24DATE: 7/21/2014
 PROJECT: GREEN TERRACE I-56
 PERMIT#: 14070420
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC 314.27(D) BOXES AT CEILING-SUSPENDED
 (PADDLE) FAN OUTLETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]