| 2014-07-12 09:14:09 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXISTING ROOF COVERING IS ASPHALT SHINGLES AND | | | THE PROPOSED ROOFING MATERIAL IS CONCRETE TILE. BECAUSE | | | OF THE DIFFERENCE IN WEIGHT OF THE TWO ROOFING | | | MATERIALS THE ROOF STRUCTURE WILL NEED TO BE EVALUATED | | | BY A FLORIDA LICENSED ENGINEER TO DETERMINE THAT THE | | | EXISTING STRUCTURE IS CAPABLE OF SUPPORTING THE | | | ADDITIONAL DEAD LOAD. SUBMIT TWO COPIES OF THE SIGNED | | | AND SEALED EVALUATION REPORT. FBCR 301.1 & CITY | | | AMENDMENTS 107.2.1.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|