| Plan Review Notes For Permit 14070408 |
| Permit Number |
14070408 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-30 10:28:41 | DATE: 7/29/2014 | | | PROJECT: 1801 PALM BEACH LAKES BOULOVARD. PBLOM PILON | | | SIGN | | | PERMIT#: 14070408 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) ELECTRICAL PLANS ARE REQUIRED TO OUTLINE THE FULL | | | EXTENT OF THE ELECTRICAL SCOPE. THE PLANS ARE REQUIRED | | | TO INDICATE COMPLIANCE WITH NEC 300 FOR WIRING | | | MEATHODS, NEC 600.6 FOR REQUIRED DISCONNECT AND | | | COMPLIANCE WITH THE FBC-ENERGY CHAPTER 5 SECTION 505.2 | | | FOR EXTERIOR LIGHTING CONTROLS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASAE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARETIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|