| 2014-07-23 16:20:51 | PLUMBING PLAN REVIEW |
| | PERMIT: 14070406 |
| | ADD:101 N CLEMATIS ST SUITES 120 & 130 |
| | CONT: CHANDLER |
| | TEL: (561)791-6934 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED JULY 23/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET P3.1 DETAIL # 6 SHOWS A/C CONDENSATE BEING |
| | DRAINED INTO A SANITARY DRAIN WITH A SINK TAIL PIECE |
| | ADAPTOR FOR A DISHWASHER WASTE. |
| | PLEASE PROVIDE COMPLIANCE WITH: |
| | 2010 FBC-PLUMBING 314.2.1 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL |
| | BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED |
| | PLACE OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| | LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (1-PERCENT SLOPE). CONDENSATE SHALL NOT |
| | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO |
| | CAUSE A NUISANCE. AN APPROVED PLACE OF DISPOSAL IS ROOF |
| | DRAINS, FRENCH DRAINS, ETC... |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |