| 2014-07-15 10:57:23 | DATE: 7/14/2014 | | | PROJECT: PANEL CHANGE 216 ARLINGTON RD | | | PERMIT#: 14070398 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PANELS CANNOT BE LOCATED IN BATHROOMS. THE PANEL | | | SCHEDULE SUBMITTED INDICATED THE LOCATION OF THE PANEL | | | IS IN THE BATHROOM. THIS IS NOT ALLOWED PER NEC | | | 240.24(E) | | | | | | 2) A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE | | | GROUND NEC 250.94 | | | | | | 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | | 314.3 AND 314.3.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WPCONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBMI | | | TTAL_FORM_04132010.PDF. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND | | | LEAVE THE PREVIOUSLY REVIEWED SHEETS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|